600/1000V 4 core armoured cable

Cross Section of Conductor No. of Wires Thickness of Insulation Thickness of Inner Sheath Thickness of Steel Tape No./Dia. Of Steel Wires Thickness of Sheath Overall Diameter Approx. Net Weight
STA SWA
STA SWA STA SWA STA SWA Al Conductor Cu Conductor Al Conductor Cu Conductor
mm2 - mm mm mm No./mm mm mm mm mm kg/km kg/km kg/km kg/km
Four Cores with Reduced Neutral
3x35+16 16-7 1.2-1 1 0.2 43/1.6 1.9 2 28.5 31.3 1107 1528 1705 2469
3x50+25 18-16 1.4-1.2 1.2 0.2 40/2.0 2.0 2.1 32.2 36.1 1410 2044 2326 3388
3x70+35 18-16 1.4-1.2 1.2 0.2 44/2.0 2.0 2.2 35.2 39.3 1733 2801 2762 4285
3x95+50 36-18 1.6-1.4 1.2 0.5 41/2.5 2.3 2.5 42.5 46.3 2656 3820 3816 5925
3x120+70 36-18 1.6-1.4 1.4 0.5 45/2.5 2.4 2.6 45.6 49.4 3137 4777 4391 7103
3x150+70 36-18 1.8-1.4 1.4 0.5 49/2.5 2.6 2.7 49.9 53.6 3660 5709 5043 8272
3x185+95 36-36 2-1.6 1.4 0.5 55/2.5 2.6 2.9 54.5 58.5 3445 7171 5902 9987
3x240+120 60-36 2.2-1.6 1.6 0.5 62/2.5 2.9 3.1 61.6 65.3 5441 9272 7174 12552
3x300+150 60-36 1.4-1.8 1.6 0.5 67/2.5 3.8 3.2 65.9 69.6 6494 11546 8355 15067
Four Cores
4x25 16 1.2 1 0.2 38/1.6 1.8 1.9 25.3 28 934 1576 1450 2092
4x35 16 1.2 1 0.2 41/1.6 1.8 1.9 27.4 30.2 1120 2017 1681 2578
4x50 18 1.4 1 0.2 39/2.0 2 2.1 31.6 35.6 1454 2658 2336 3540
4x70 18 1.4 1.2 0.5 43/2.0 2.1 2.2 36.3 39 2183 3916 2840 4573
4x95 36 1.6 1.2 0.5 50/2.0 2.3 2.4 40.6 44.1 2748 5160 3545 5957
4x120 36 1.6 1.4 0.5 42/2.5 2.4 2.5 43.9 47.2 3237 6214 4334 7372
4x150 36 1.8 1.4 0.5 48/2.5 2.5 2.6 48.3 52 3853 7622 5148 8917
4x185 36 2 1.6 0.5 54/2.5 2.7 2.8 54.3 57.6 4756 9323 6132 10774
4x240 60 2.2 1.6 0.5 59/2.5 2.9 3 59.2 62.9 5774 11906 7374 13506
4x300 60 2.4 1.6 0.5 65/2.5 3 3.2 64.3 68.1 6922 14589 8624 16291