0.6/1KV 2.5mm2 3 Core Armoured Cable

Main technical characteristics:
 
DC resistance: conductor resistance of finished cables per km at 20℃ is not more than the following:
Cu core Ohm/km: 7.41
Al core Ohm/km: 12.1
Nominal crosssection: 50mm2
 
Voltage test each drum of finished cable should withstand power frequency voltage 3.5KV for 5 minutes, the insulation is not breakdown
 
Operating characteristics:
1) Rated power –frequency voltage UO/U is 0.6/1KV.
2) Max.permissible continuous operating temperature of conductor: 90℃.
3) Max.short –circuit temperature of conductor shall not exceed 250℃ (5s maximum duration ).
4) The ambient temperature under installation should not below 0℃.
5) The bending radius of cable are recommended as follow:
Single core cable: unarmored cable shall be not less than 20 times of the cable's OD,armored cable shall be not less than 15 times of the cable's OD.
Multi core cable: unarmored cable shall be not less than 15 times of the cable's OD, armored cable shall be not less than 12 times of the cable's OD.
 
Packaging:
Packing by wooden drum, iron wooden drum,steel wooden drum,wooden case or according to customer's requirement.
Standard:

IEC 60502, BS and other standard, also can custom accoring to customers' requirement.
0.6/1KV 2.5mm2 3 Core Armoured Cable parameter: