bs5467 specification low voltage 3 core Cu/Al conductor armoured power cables
LV 3 core armoured cableLV 3 core Cu/Al conductor armoured power cables are used for the power and control circuit, the cable steel wire armored play good protective effect. So it can be used for building interior or buried underground.
 
Structure:
Conductor: solid aluminum or copper conductor, 2 types circular or fan, follow the 6360/IEC BS 60228
 
Insulated: XLPE (XLPE) GP 8 GP or ethylene propylene rubber 6 class
 
Color coded 1 Core: Brown
2 Core: brown or blue
3 core: Brown, black, gray
4 core: blue, brown, black, gray
5 core: yellow green, blue, brown, black, gray
More than 5 cores: white line core and black digital logo
 
Inner: PVC (polyvinyl chloride)
 
Armoured: single core: AWA (aluminium wire armour)
 
Multi core: SWA (steel wire armored)
 
Outer sheath PVC (polyvinyl chloride), or anti mouse PVC (optional)

 
Technical parameter:
 
Rated voltage: 600/1000V
 
Rated temperature 0°C to +90°C
 
Bending radius: 1.5mm2 - to 16mm2: 6 x diameter
 
25mm2 - and above: 8 x diameter
 
Fireproofing: IEC60332 the first part, the first part of BS4066
LV 3 core armoured cable
Technical parameter:
 
600/1000V three conductor multistrand copper conductor power cable parameter:
 
Nominal conductor cross-sectional area Stranded type Nominal thickness of insulation Nominal lining thickness Nominal steel wire armoured diameter Nominal sheath thickness Nominal diameter Nominal weight
Extrusion type lining Tape lined
mm² No./mm mm mm mm mm mm mm kg/km
3x1.5 7/0.53 0.6 0.8 0.9 1.3 12.6 - 340
3x2.5 7/0.67 0.7 0.8 0.9 1.4 14.1 - 408
3x4 7/0.85 0.7 0.8 0.9 1.4 15.3 - 498
3x6 7/1.04 0.7 0.8 0.9 1.4 16.6 - 600
3x10 7/1.35 0.7 0.8 1.25 1.5 19.5 - 915
3x16 7/1.70 0.7 0.8 1.25 1.6 21.6 21.6 1130
3x25 7/2.14 0.9 1 1.6 1.7 26.7 26.3 1710
3x25* 7/2.14 0.9 1 1.6 1.7 23.6 23.2 1710
3x35 7/2.52 0.9 1 1.6 1.8 29.4 29.0 2100
3x35* 7/2.52 0.9 1 1.6 1.8 25.7 25.3 2100
3x50* 19/1.78 1.0 1 1.6 1.8 28.5 28.1 2450
3x70* 19/2.14 1.1 1 1.6 1.9 32.2 31.8 3120
3x95* 19/2.52 1.1 1.2 2.0 2.1 37.0 36.2 4310
3x120* 37/2.03 1.2 1.2 2.0 2.2 40.4 39.6 5160
3x150* 37/2.25 1.4 1.4 2.5 2.3 45.5 44.3 7160
3x185* 37/2.52 1.6 1.4 2.5 2.4 49.8 48.6 8600
3x240* 61/2.25 1.7 1.4 2.5 2.6 55.1 53.9 10755
3x300* 61/2.52 1.8 1.6 2.5 2.7 60.2 58.6 13080
3x400* 61/2.85 2 1.6 2.5 2.9 66.6 65.0 15810
 
600/1000V three conductor solid aluminum conductor power cable parameter:
 
Nominal conductor cross-sectional area Nominal thickness of insulation Nominal thickness of lining Nominal diameter aluminium wire armoured Armoured tape Nominal sheath thickness Nominal diameter Nominal cable weight
thickness width Aluminium wire armoured Aluminium strip armoured
Extrusion type lining tape lined
mm² mm mm mm mm mm mm mm mm mm kg/km
3x16 0.7 0.8 1.25 0.6 2.4 1.6 20.3 20.3 19 760
3x25 0.9 1 1.6 0.6 2.4 1.7 22.5 22.1 20.1 1020
3x25* 0.9 1 1.6 0.6 2.4 1.7 24.9 24.5 22.5 1020
3x35 0.9 1 1.6 0.6 2.4 1.8 24.4 24.9 22 1200
3x35* 0.9 1 1.6 0.6 2.4 1.8 27.3 26.9 24.9 1200
3x50* 1.0 1 1.6 0.6 2.4 1.8 26.8 26.4 24.9 1380
3x70* 1.1 1 1.6 1 3.6 1.9 30.2 29.8 28.6 1750
3x95* 1.1 1.2 2.0 1 3.6 2.1 34.8 34.0 32 2420
3x120* 1.2 1.2 2.0 1.4 4.8 2.2 37.8 37.0 35.8 2820
3x150* 1.4 1.4 2.5 1.4 4.8 2.3 42.7 41.5 39.3 3660
3x185* 1.6 1.4 2.5 1.4 4.8 2.4 46.7 45.5 43.3 4350
3x240* 1.7 1.4 2.5 1.4 4.8 2.6 51.5 50.3 48.1 5220
3x300* 1.8 1.6 2.5 1.8 6.4 2.7 56.2 54.6 53.2 6200