YJV 50 mm armoured cable
YJV 50 mm armoured cable
 
YJ---- crosslinked polyethylene insulation(XLPE)
V---- PVC sheathed
 
The name of the YJV cable type: cross-linked polyethylene insulated PVC sheathed power cable
 
50mm armoured cable:
This product is applicable for the AC circuit of rated voltage up to 0.6/1KV, used in power transmission and distribution system.
 
50mm armoured cableProduct Description:
1. Conductors: copper or aluminum.
2. Both armored and non-armored type power cables are available.
3. Voltage rating: 0.6/1KV,1.8/3KV, 3.6/6KV, 35kV
4. PVC or PE sheathed.
5. Number of cable cores: one core(Single core),two cores(Double cores),three cores, Four cores (Four Equal-section-area cores or three equal-section-area cores and one smaller section area neutral core), Five cores (Five equal-area cores or three equal-section-area cores and two smaller section area neutral cores).
6. Standards: IEC 60502. IEC, BS, DIN, ASTM, CSA, NFC, AS, GOST etc. Or other special characteristics as customers request.
 
Colour Code:
Colour Code (1) : 
1 Core : Red or Black
2 Cores : Red, Black
3 Cores : Red, Yellow, Blue
4 Cores : Red, Yellow, Blue, Black
5 Cores : Red, Yellow, Blue, Black, Green
Above 5 Cores : Black Cores with White numerals
Colour Code (2) : 
1 Core : Brown or Blue
2 Cores : Brown or Blue
3 Cores : Brown, Black, Grey
4 Cores : Blue, Brown, Black, Grey
5 Cores : Green/Yellow, Blue, Brown, Black, Grey
 
Power cable's characteristic:
1) long time operating temperature for cable conductor is 90 degrees.
2) the highest temperature of the conductor in short circuit (no longer than 5 seconds) in not more than 250 degree
if a joint is in the cable, the temperature of the tinning welding joint is not more than 120 degrees, compressing joint not more than 150 degrees and electro-welding joint not more than 250 degrees.
3) no drop in limited provided there is full mechanical tention when cable is laid. It si forbidden to lay cable in iron-pipe or to fix cable by circling around the cable with iron materials.
4) being laid, the minimum temperature of the cable shall not be lower than zero degree. In the caselowtemperature, heating measures shall be taken.
 
 

Contact Form Please fill all the texts in the fields.