600/1000v five core cable - PVC power cable and XLPE insulated armoured power cable
Five core cable has five mutually insulated core wire, and outside wrapped the five core wire plastic sheath or steel armor with plastic sheath.
Five core cable
Five core cable structure:
Including five conductors with insulating layer, in each conductor is provided with a protection layer, which a conductor cross section is round, flat structure, in addition four core conductors cross section are corrugated shape structure, outside is circular, inside is linear, four section corrugated conductors in the way of inner inward distribute in the circular cross section conductor surrounding, and between the conductors fill filler.
 
Use:
Five core cable is composed of 5 mutually insulated stranded conductors, Outer with a protection layer. commonly used in three-phase four wire system.
 
->> Rated voltage 0.6/1kV five core PVC insulated armoured power cable:
five core PVC insulated armoured power cable
This cable adopts neutral wire and ground wire.
 
The rated voltage of the cable should be suitable for the operating conditions of the cable system, in order to facilitate the selection of cable, the system is divided into the following three class:
 
Class A: when any phase conductor is in contact with the ground or ground conductor, the system can be separated in a minute.
 
Class B: can be used in single phase ground fault for a short time, according to JB/T8996 regulations, grounding fault time is not more than 1 hours, for this standard cable allows a longer time to run, but in any case should not exceed 8 hours, the total duration time of the fault is not more than 125 hours.
 
Class C: systems that not belong to class A, class B.
 
Rated voltage 0.6/1kV five core PVC insulated power cable model:
 
VV22,VLV22: PVC insulation PVC sheath steel tape armoured power cable
VV32,VLV32: PVC insulation PVC sheath fine steel wire armoured power cable
VV42,VLV42: PVC insulation PVC sheath thick steel wire armoured power cable
VV23,VLV23: PVC insulation PE sheath steel tape armoured power cable
VV33,VLV33: PVC insulation PE sheath fine steel wire armoured power cable
VV43,VLV43: PVC insulation PE sheath thick steel wire armoured power cable
 
0.6/1kV five core PVC insulated armoured power cable features:
 
The maximum temperature of PVC insulated armoured power cable conductor is 70℃, and the short circuit temperature (longest for 5S) is 160℃.
 
Ambient temperature for cable installation:
 
The environment temperature should not be lower than 0℃.
 
The minimum bending radius of the cable is 12D (D is cable diameter).
 
->> Rated voltage 0.6/1kV five core XLPE insulated armoured power cable:
 
This cable adopts neutral wire and ground wire.
 
The rated voltage of the cable should be suitable for the operating conditions of the cable system, in order to facilitate the selection of cable, the system is divided into the following three class:
 
Class A: when any phase conductor is in contact with the ground or ground conductor, the system can be separated in a minute.
 
Class B: can be used in single phase ground fault for a short time, according to JB/T8996 regulations, grounding fault time is not more than 1 hours, for this standard cable allows a longer time to run, but in any case should not exceed 8 hours, the total duration time of the fault is not more than 125 hours.
 
Class C: systems that not belong to class A, class B.
 
Rated voltage 0.6/1kV five core XLPE insulated power cable model:
 
YJV22,YJLV22: XLPE insulation PVC sheath steel tape armoured power cable
YJV32,YJLV32: XLPE insulation PVC sheath fine steel wire armoured power cable
YJV42,YJLV42: XLPE insulation PVC sheath thick steel wire armoured power cable
YJV23,YJLV23: XLPE insulation PE sheath steel tape armoured power cable
YJV33,YJLV33: XLPE insulation PE sheath fine steel wire armoured power cable
YJV43,YJLV43: XLPE insulation PE sheath thick steel wire armoured power cable
 
0.6/1kV five core XLPE insulated armoured power cable features:
 
The maximum temperature of PVC insulated armoured power cable conductor is 90℃, and the short circuit temperature (longest for 5S) is 250℃.
 
Ambient temperature for cable installation:
 
The environment temperature should not be lower than 0℃.
 
The minimum bending radius of the cable is 12D (D is cable diameter).
 

Contact Form Please fill all the texts in the fields.

Newslist
About Us Products News Download Contact Us

Copyright © 2018 Henan Jiapu Cable Group All Rights Reserved Power by DedeCms