4c x 185 mm2 + 1c x 95 mm2 xlpe swa lsf cable
4c x 185 mm2 + 1c x 95 mm2 xlpe swa lsf cable
 
The main features of the flame retardant XLPE power cable is hard to catch on fire or that the continous burning of cables is very limited when it is on fire, it applies to the places with many cables laid tightly together such as powergenerated station, subway, tunnel, high-storey building and other places concerning to fire security and its lifesaving.
 
The main characteristics of low smoke, halogen-free, flame retardant power cable is very low smoke and harmless (low toxic, low corrosive) besides the proterty of flame retardant. It can be used in such kinds of places, such as subway, tunnel, power station with special demands of property of flame retardant, the density of smoke emission and toxic index if cable is burnt.
 
Key technical parameter:
Calculation condition of the ampacity:
ambient temperature is 25 degree.
conductor working temperature: 90 degree
soil heat resulted from water migration when it operated continuously.
gap between cable and surface of ground is 1000 millimeter when it is laid in ground.
for multicore cable, gap of cable is 3 times OD.
 
4c x 185 mm2 + 1c x 95 mm2 xlpe swa lsf cable
 
0.6/1KV 4*185+1*95 YJV, YJLV Low smoke zero halogen cable parameter:
Reference overall diameter of cable (mm): 56.8
Permissible Ampacity in air: 433
Permissible Ampacity in ground: 418
Reference weight of cable (kg/km): 9191
 
0.6/1KV 4*185+1*95 YJV22, YJLV22 Low smoke zero halogen cable parameter:
Reference overall diameter of cable (mm): 62.2
Permissible Ampacity in air: 433
Permissible Ampacity in ground: 408
Reference weight of cable (kg/km): 10606