British standard BS 6883 swa flexible cable colours
 

Armoured power flexible cable is suitable for installation in mechanical maintenance ship or offshore. A series of size artificial common cable can be used to control and power equipment. This kind of cable applies equally the masses and instrument shore in case of a fire.
 
Rated voltage 0.6/1kV
 
Conductor BS6360 2 class or 5 class conductor
(5 types are usually required to make)
 
Rated temperature +90°C maximum conductor temperature
 
Static rated temperature -30°C to +90°C
The bending radius (static) ≤25 mm2 - 4 x cable diameter
 
>25 mm2 - 6 x cable diameter
 
Flame retardant part 3A BS4066, part 3A IEC60332
 
Color coding:
 
A) color coding
 
1 core red or black
 
2 core red, black
 
3 core red, yellow, blue
 
4 core red, yellow, blue, black
 
5 core and above, in sequence coding

Technical parameter:
 
Conductor nominal cross-sectional area
(mm2/font)
Inner sheath outer diameter
min-max mm
Outer sheath diameter
min-max mm
Single core cable
1 4.7 - 5.8 8.3 - 9.8
1.5 5.0 - 6.2 8.5 - 10.1
2.5 5.4 - 6.6 8.9 - 10.5
4 6.3 - 7.6 9.8 - 11.7
6 6.8 - 8.1 10.4 - 12.2
10 7.7 - 9.1 11.5 - 13.4
16 8.9 - 10.3 12.7 - 14.6
25 11.1 - 12.8 15.0 - 17.3
35 12.0 - 13.7 16.1 - 18.4
50 13.7 - 15.5 17.9 - 20.2
70 15.5 - 17.4 19.8 - 22.6
95 17.7 - 19.8 22.2 - 25.2
120 19.6 - 22.0 24.3 - 27.3
150 21.6 - 24.2 26.5- 29.7
185 24.0 - 26.6 29.8 - 33.5
240 27.1 - 29.9 33.1 - 36.9
300 30.0 - 33.2 36.2 - 40.1
400 33.8 - 37.1 40.3 - 44.8
500 37.6 - 41.1 44.5 - 49.2
630 41.2 - 45.2 48.4 - 53.6