1200 mw xlpe cable resistance
Cable insulation resistance value is related with the cable type, voltage grade and cable insulation temperature, wet air degree, environmental dust properties and cable using life.
 
XLPE insulated PVC sheathed power cable, 20℃, per kilometer length of insulation resistance minimum value is:
 
Rated voltage 6kV, conductor section 16 - 35mm2, generally not less than 1000MΩ; conductor section 50 - 95mm2, generally not less than 750MΩ; conductor section 120 - 240mm2, generally not less than 500MΩ.
 
Rated voltage 10kV, conductor section 16 - 35mm2, generally not less than 2000MΩ; conductor section 50 - 95mm2, generally not less than 1500MΩ; conductor section 120 - 240mm2, generally not less than 1000MΩ.
 
Insulation resistance conversion formula: R20= Rt×k×L/1000
In which: R20—20℃ insulation resistance, MΩ.km
Rt—The insulation resistance measured values, MΩ;
k—Insulation resistance temperature conversion factor;
L—The length of the sample, m
 
0℃ temperature coefficient is 0.48; 5℃ the coefficient is 0.57; 10℃ coefficient is 0.70; 15 ℃ coefficient is 0.85; 20 ℃ 
the coefficient is 1.0, 25℃ the coefficient is 1.13; 30 ℃ the coefficient is 1.41, 35℃ the coefficient is 1.66, 40 ℃ the coefficient is 1.92.